AFP-3030 Operations Manual — P/N DOC-01-033:C 05/12/2018 39Control Module Read Status3.7 Control ModuleWhen a module address is entered into the Point Select Screen and the ACCEPT soft key is pressed, the following screen will display ifthe module is a control module.Figure 3.8 Control Module Screen - Read StatusDisplayLines 1 through 10 - Refer to the descriptions in Section 3.2, “Smoke Detector”, on page 35 with the exception of line 6, which isdescribed below.Line 6 - This line displays statistics that display for control module output points; in the above example they are:AUTOMATIC OFFThe first field displays the point control. There are four designations that could appear in this fieldThe second field displays the point status. There are three designations that could appear in this field.The device is a control module (an output device) so by referring to the descriptions below, it can be determined that the point is in a nor-mal state.Outputs: (Control Modules)If the point is not in fault or disabled and the status is Automatic, the display will read:AUTOMATIC OFFAUTOMATIC ONAUTOMATIC OFF-HOOKIf the point has been forced into a manual control state, the display will read as follows. will appear when there is a pointfault.MANUAL OFF *MANUAL ON *MANUAL OFF-HOOK *If the point is disabled, the display will read as follows. will appear when there is a point fault.DISABLED OFF *DISABLED ON *DISABLED OFF-HOOK *If the point is in fault, the display will read:FAULT OFF *Point ControlDesignation DescriptionAUTOMATIC The point is being controlled automatically by the panel.MANUAL The point has been forced into manual control state by an outside source.DISABLED A status change other than a change to MANUAL control has caused thepoint to go off automatic control.FAULTTable 3.4Point StatusDesignation DescriptionOFF The point is currently not activated.ON The point is currently activated.OFF-HOOK The telephone point is currently off-hook.Table 3.5L A K E V I E W G E N E R A L H O S P I T A LS Y S T E M N O R M A L1 0 : 2 2 : 3 4 A T U E J A N 2 2 , 2 0 1 9R E A D A D D R E S S : N 1 2 4 L 0 3 M 0 5 2A U T O M A T I C O F FE L E V A T O R L O B B Y E A S T W I N GF I F T H F L O O R Z 0 0 5 C O N T R O LZ 0 0 5 , Z 0 2 7 , Z 0 6 6 , , ,, , , , ,W A L K T E S T : Y E SS W I T C H I N H I B I T : Y E SS I L E N C E A B L E : Y E S - R E S O U N D F I R E1 0 : 2 2 : 3 4 A T U E J A N 2 2 , 2 0 1 9 B A C K