NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 29Active Trouble Monitor Mode of Operation Operation of the Control Panel3.10.2 How the Control Panel Indicates an Active Fire ControlActivation of a FIRE CONTROL point causes the control panel to do the following:• Initiate the monitor module Control-by-Event• Send a message to the LCD display, History buffer and installed printers, FDU-80annunciators, and CRT-2s• Display an ACTIVE status banner and FIRE CONTROL Type Code on the LCD display, along withinformation specific to the deviceFigure 3.13 Sample Fire Control Point Display3.10.3 How the Control Panel Indicates an Active Non-Fire PointNon-Fire point operation does not affect control panel operation, nor does it display a message atthe panel LCD. Activation of a Non-Fire point activates CBE—but does not cause any indicationon the control panel. For example, you can program a Non-Fire point to turn lights in a zone to alower setting when activated. In this case, when the point activates the control panel activates thepoint’s CBE to turn the lights down without any audio or visual indication on the control panel.3.11 Active Trouble Monitor Mode of Operation3.11.1 How the Control Panel Indicates an Active Trouble MonitorTrouble Monitor Points are monitor modules programmed with the following Type Codes:These types of monitor modules operate like monitored system functions that can producetroubles—but with the following differences:• The LCD display status banner displays ACTIVE as shown:Figure 4 Sample Trouble Monitor Point Message• The monitor module is non-latching: the module will return to normal when the troublecondition no longer exists.• The monitor modules activate Control-by-EventStatus bannerType CodeZone affected by the Fire ControlA C T I V E F I R E C O N T R O L I N T E N S I V E C A R E U N I TE A S T E R N W I N G Z 0 5 5 0 8 : 5 9 a 0 1 1 5 1 1 1 M 0 4 4Type Code Latching(Y/N) Device Function Point FunctionEQUIP MONITR N Used for recording access to monitored equipment Activates CBEPOWER MONITR N Used to monitor remote power supplies or otherexternal equipmentIndicates troubleTROUBLE MON N Used to monitor remote power supplies or otherexternal equipmentIndicates troubleTable 3.6 Trouble Monitor Type CodesStatus bannerType CodeT R O U B L T R O U B L E _ M O N I N T E N S I V E C A R E U N I TE A S T E R N W I N G 0 9 : 3 8 A 0 1 1 5 1 1 1 M 0 4 4Custom descriptor forthis device locationDevice addressTime and date of troubleExtended 12 charactercustom label