NFS-320/E/C, NFS-320SYS/E Operations Manual — P/N 52747:E1 06/16/2011 61Operating Modes Remote Terminal AccessC.2.2 Local Monitor Mode (LocM)Functions, passwords, and special requirements of Local Monitor Mode (LocM) are:Functions available with the Local Monitor Mode:C.2.3 Remote Terminal Mode (RemT)Functions, passwords, and special requirements of Remote Terminal Mode (RemT) are:Control Functions • Acknowledge.• Signal Silence.• System Reset.• Drill.Function Lets you...Table C.1 Local Terminal Mode Functions (2 of 2)Functions: Read Status, Alter Status, and Control Functions (Table C.2).Passwords: User-defined password for Alter Status and Control functions.Requirements: Password security feature for Control Functions eliminates the need for mounting theCRT-2 in an enclosure.Function Lets you...Read Status • Display the status of an individual point (Detector, Module, or Zone).• Display a list of all the points in Alarm or trouble.• Display a list of all programmed points in the system.• Step through the History buffer event by event.• Display the entire History buffer.Alter Status • Disable/Enable an individual point.• Change the sensitivity of a detector.• Clear the verification counter of all detectors.• Clear the entire History buffer.• Set the Intelligent Sensing alert and action levels.Control Functions • Acknowledge• Signal Silence• System Reset• DrillTable C.2 Local Monitor Mode FunctionsFunctions: Read Status only. See Table C.3.Passwords: NoneRequirements: Use with UL ITE-listed terminals, including personal computers with the VeriFire™Tools or terminal emulation software. Intended for terminals connected throughmodems, including FSK modems connected through a public switched telephonenetwork.