8.1.4. Soft Dry Operation8.1.4.1. Thermostat control• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -2.5°C.• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFFpoint.8.1.5. Heating Operation8.1.5.1. Thermostat control• Compressor is OFF when Intake Air Temperature - Internal Setting > +1.5°C.• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature < Compressor OFFpoint -0.5°C.8.1.6. Automatic OperationThis mode can be set using remote control and the operation is decided by remote control setting temperature, indoor intake airtemperature and outdoor air temperature.During operation mode judgment, indoor fan motor (with speed of Lo-) and outdoor fan motor are running for 30 seconds to detectthe indoor intake and outdoor air temperature. The operation mode is decided based on below chart.17CS-E24DKE CU-E24DKE