8.2.2. Protection Control For Cooling & Soft Dry Operation8.2.2.1. Outdoor Air Temperature ControlThe compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.8.2.2.2. Cooling Overload Controli. Pipe temperature limitation/restriction• Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation frequency)• The compressor stop if outdoor pipe temperature exceeds 62°C• If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95: outdoor high pressure rise protection)ii. Electrical part temperature rise protection control• To prevent electrical component temperature rise during cooling overload.• Judgement condition is by outdoor temperature (sampled every 10s).• Control contents:Outdoor fan speed (switch to zone A and B minimum fan speed).Outdoor total current (zone C) higher than the specified.• Cancellation condition: When one of above is not satisfied.34CS-E24DKE CU-E24DKE