6814.8 Timer Control There are 2 sets of ON and OFF timer available to turn the unit ON or OFF at different preset time. If more than one timer had been set, the upcoming timer will be displayed and will activate in sequence.14.8.1 ON Timer Control ON timer 1 and ON timer 2 can be set using remote control, the unit with timer set will start operate earlier thanthe setting time.This is to provide a comfortable environment when reaching the set ON time. 60 minutes before the set time, indoor (at fan speed of Lo-) and outdoor fan motor start operate for 30 seconds todetermine the indoor intake air temperature and outdoor air temperature in order to judge the operation startingtime. From the above judgment, the decided operation will start operate earlier than the set time as shown below.14.8.2 OFF Timer ControlOFF timer 1 and OFF timer 2 can be set using remote control, the unit with timer set will stop operate at set time.14.9 Auto Restart Control When the power supply is cut off during the operation of air conditioner, the compressor will re-operate withinthree to four minutes (there are 10 patterns between 2 minutes 58 seconds and 3 minutes 52 seconds to beselected randomly) after power supply resumes. This type of control is not applicable during ON/OFF Timer setting. This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board.14.10 Indication PanelLED POWER TIMER ECONAVI +8/15°C HEAT DEICEColor White White White White WhiteLight ON Operation ON Timer Setting ON ECONAVI ON +8/15°C HEAT ON DEICE ONLight OFF Operation OFF Timer Setting OFF ECONAVI OFF +8/15°C HEAT OFF DEICE OFFNote: If POWER LED is blinking, the possible operation of the unit are Hot Start, operation mode judgment, or ON timersampling. If Timer LED is blinking, there is an abnormality operation occurs.