7417.4 Self-diagnosis Method17.4.1 H11 (Indoor/Outdoor Abnormal Communication)Malfunction Decision Conditions During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signaltransmission is checked whether it is normal.Malfunction Caused Faulty indoor unit PCB. Faulty outdoor unit PCB. Indoor unit-outdoor unit signal transmission error due to wrong wiring. Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between theindoor and outdoor units. Indoor unit-outdoor unit signal transmission error due to disturbed power supply waveform.TroubleshootingCheck the indoor-outdoor units’ connection wires.Is there any wiring error?Disconnect terminal 3 wire and measure Vdc between terminal2 & 3 from the outdoor unit.Reconnect terminal 3 wire and measure Vdc between terminal2 & 3 from the outdoor unit.Is the Vdc fluctuate between 10~70Vdc?Is the Vdc fluctuate between 10~70 Vdc?When abnormality indication starts again.For safety reason and to preventcomponent breakdown, always switchoff the power before remove andconnect the component.Replace indoor unit PCB.Replace outdoor PCB.Correct the indoor-outdoor unitsconnection wires.NONONOYESYES