9617.4.23 F90 (Power Factor Correction Protection)Malfunction Decision Conditions To maintain DC voltage level supply to power transistor. To detect high DC voltage level after rectification.Malfunction Caused During startup and operation of cooling and heating, when Power Factor Correction (PFC) protection circuitry atthe outdoor unit main PCB senses abnormal DC voltage level for power transistors. When DC voltage detected is LOW, transistor switching will turn ON by controller to push-up the DC level. When DC voltage detected is HIGH (391Vdc – 425Vdc), active LOW signal will send by the controller to turn OFFrelay RY-C.TroubleshootingWhen abnormality indication starts again.Reset the error code and turn on the unit again.Is AC power supply normal fluctuation?Verify PFC abnormality by measuring DC voltage betweenDCP(+) and DCN(-) at the capacitor PCB.Is the DC voltage between DCP(+) and DCN(-) normal?Check the reactor impedance.Is the impedence of the reactor low?Is the DC voltage between CN-FM1 and 4 of the outdoor fanmotor normal?Are the compressor’s winding resistance (U-V, V-W, U-W)uniform?Confirm the DC voltage between CN-FM 1 and 4 whencompressor is running. Normal voltage range should bebetween 265-325Vdc.NOYESYESYESNO (391.2Vdc ~ 425Vdc)● AC power supply abnormal surge.YES (~280Vdc) ● Defect in PFC circuitry.● Replace the outdoor unit PCB.NO ● Defect in outdoor fan motor.● Replace outdoor fan motor.NO ● Defect in compressor.● Replace compressor.● Defect in reactor.● Replace reactor.For safety reason and to preventcomponent breakdown, alwaysswitch off the power before removeand connect the component.Check the compressor winding resistance:● Turn off the power and disconnect the harnesses U, V,and W.● Measure the winding resistance between U-V, V-W, andW-U.