CompHz = Freq. A × Freq. H + Freq. CExample Calculation:Model No.: XE9CKOperation Mode: CoolingWhen Intake Air Temperature - Internal setting Temperature:1.5°CCompHz = Freq. A × Freq. H + Freq. C= 1.9 × 20 + 1.0= 39 Hz (It cuts down less than a decimal point)Cooling & Soft Dry XE9CK XE12CKFreq. A Freq. C Freq. A Freq. CLow Load (Freq. H 10) 0.9 11.0 0.9 11.0High Load (Freq. H > 10) 1.9 1.0 1.9 0.7Heating XE9CK XE12CKFreq. A Freq. C Freq. A Freq. CLow Load (Freq. H 12) 1.4 10.6 1.4 10.6High Load (Freq. H > 12) 2.2 1.0 2.1 1.8Freq. Range XE9CK XE12CKCooling Fc 39 52Operation Range 12 ~ 86 12 ~ 102Heating Fh 56 69Operation Range 14 ~ 128 14 ~ 1288.1.2. Compressor Operation FrequencyZone Intake Air Temperature - Internal Setting Temperature (°C) Freq. HCooling Soft Dry Heating Cooling Soft Dry Heating RemarkXE9CK XE12CK XE9CK XE12CK XE9CK XE12CK1 -2.0 -3.0 1.0 2 1 5 5 1 12 -1.5 -2.5 0.5 2 5 10 10 3 83 -1.0 -2.0 0.0 4 8 10 10 6 134 -0.5 -1.5 -0.5 9 12 10 12 11 185 0.0 -1.0 -1.0 11 14 12 14 15 236 0.5 -0.5 -1.5 14 18 12 17 18 277 1.0 0.0 -2.0 17 22 14 17 21 308 1.5 0.5 -2.5 20 27 14 20 25 32 Fc, Fh9 2.0 1.0 -3.0 20 27 16 24 25 32 Fc, Fh10 2.5 1.5 -3.5 20 27 20 27 25 32 Fc, Fh11 Nil Nil -4.0 Nil Nil Nil Nil 25 32 Fh12 Nil Nil -4.5 Nil Nil Nil Nil 25 32 FhOperating Frequency Calculation Formula:Remarks:When Freq. H is equal to 20 (XE9CK), 27 (XE12CK) for cooling, 25 (XE9CK), 32 (XE12CK) for heating or above, the Comp.may run at the freq. higher than Fc or Fh up to max. freq. operation.Best Amenity ControlEvery 90s (Cooling), 120s (Heating) maintain same zone Freq. H + 1 until Fc, Fh.8.1.3. Cooling Operation8.1.3.1. Thermostat control•••• Compressor is OFF when Intake Air Temperature - Internal Setting Temperature < -1.5°C.•••• Compressor is ON after waiting for 3 minutes, if the Intake Air Temperature - Internal Setting Temperature > Compressor OFFpoint.17CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKEPanasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oywww.ilmalämpöpumput.com