8.1.16.2. Ionizer Operation case studyCase 18.2. PROTECTION CONTROL FEATURES8.2.1. Protection Control For All Operations8.2.1.1. Time Delay Safety Control1. The compressor will not start for three minutes after stop of operation.2. This control is not applicable if the power supply is cut off and on again or after 4-way valve deices condition.8.2.1.2. 30 Seconds Forced Operation1. Once the compressor starts operation, it will not stop its operation for 30 seconds.2. However, it can be stopped using remote control or Auto Switch at indoor unit.8.2.1.3. Total Running Current Control1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will bedecreased.2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for three minutes.XE12CK XE9CKOperation Mode X (A) Y (A) X (A) Y (A)Cooling/Soft Dry (A) 6.5 17.0 4.5 17.0Cooling/Soft Dry (B) 6.0 17.0 4.0 17.0Heating 9.2 17.0 6.1 17.030CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKEPanasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oywww.ilmalämpöpumput.com