Values of T1, T2, and T3 depend on remote control setting temperature, as shown in below table. After the adjustment of T1, T2and T3 values, the operation mode for that particular environment and remote control setting is judged and performed, based onthe above operation mode chart, every 30 minutes.Remote Control Setting Temperature (°C) T1 T2 T316 ~ 18 +10 +8 -519 ~ 22 +8 +7 -723 ~ 26 +7 +6 -727 ~ 30 +6 +5 -8There is a temperature shifting on T1, T2, and T3 if the operation mode judged is changed from Cooling/Soft Dry to Heating or viceverse.Operation Mode change from Temperature shifts (°C)Cooling/Soft Dry → Heating -2Heating → Cooling/Soft Dry +2Example of operation mode chart adjustment:From the above table, if remote control setting temperature = 25,T1 = 25 + 7 = 32; T2 = 25 + 6 = 31; T3 = 25 - 7 = 18The operation mode chart for this example is as shown in below figure and the operation mode to be performed will depend onindoor intake air temperature and outdoor air temperature at the time when the judgment is made.8.1.7. Indoor Fan Motor OperationA. Basic Rotation Speed (rpm)•••• Required rotation speed for fan is set to respond to the remote control setting (10 rpm unit)[Cooling, Dry, Fan]Remote Control — O O O O O — — —Tab (rpm) SHI Hi Me+ Me Me- Lo Lo- SLo SSLoXE9CK 1250 1200 1100 1000 900 800 780 730 720XE12CK 1340 1310 1200 1090 980 880 780 730 720[Heating]Remote Control — O O O O O — — —Tab (rpm) SSHI SHi Me+ Me Me- Lo Lo- SLo SSLoXE9CK 1350 1270 1160 1050 940 840 790 730 720XE12CK 1490 1410 1330 1250 1170 1100 840 730 72019CS-XE9CKE CU-XE9CKE / CS-XE12CKE CU-XE12CKEPanasonic ilmalämpöpumput korjaa ja huoltaa pääkaupunkiseudulla: Jäähdytinpalvelu RefGroup Oywww.ilmalämpöpumput.com