D. Deodorizing Controli. Control conditionControl at cooling/dry operation and auto fan speed.No Deodorizing Control is performed during ON timer standby operation and during Anti-freezing control prevention.ii. OperationThe odor status is arranged as below and it is shifted as follow.* When COMP is ON 1 → 2 → 3(Shift to 4 when COMP is OFF)* When COMP is OFF 4 → 5 → 6 → 7 → 6 ←→ 7(Shift to 1 when COMP is ON)* Start from 4 if the Thermostat is OFF during the start operation.Odor Status 1 2 3 4 5 6 7 6.7.6... 1Status Shiftaccording to COMPON OFF ONStatus ShiftaccordingCoolingzone 40 50 — 30 90 20 90 20.90.20...to time (s) Dry zone ONFan SpeedCoolingzone OFF SSLoAuto Fan SpeedSSLo OFF SSLo OFF SSLo.OFF...Dry zone SLo8.1.8. Outdoor Fan Motor OperationOutdoor fan motor is operated with one fan speed only. It starts when compressor starts operation and it stops 30 seconds aftercompressor stops operation.8.1.9. Airflow Direction1. There are two types of airflow, vertical airflow (directed by horizontal vane) and horizontal airflow (directed by vertical vanes).2. Control of airflow direction can be automatic (angles of direction is determined by operation mode, heat exchanger temperatureand intake air temperature) and manual (angles of direction can be adjusted using remote control).28CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKEThis document is protected (secured) by www.nettovarmepumpar.se