8.2.2.3. Anti-Freezing Control1. When indoor heat exchanger temperature is lower than 2°C continuously for six minutes, compressor will stop operating.2. Compressor will resume its operation three minutes after the indoor heat exchanger is higher than 10°C.3. At the same time, indoor fan speed increase +20 rpm compared to its normal operation.4. If indoor heat exchanger temperature is higher than 10°C for five minutes, the fan speed will return to its normal operation.8.2.2.4. Anti-Dew Formation Control1. When indoor fan speed is set at Me- or slower, the compressor operating frequency is regulated by operation time to preventfog discharged from indoor as shown in below table.rpm Operation time, T (min) E9DK E12DK0 T 30 26 Hz 39 HzBelow 710 30 T 90 26 Hz 37 Hz90 T 420 26 Hz 37 Hz0 T 30 40 Hz 59 Hz710 ~ 790 30 T 90 33 Hz 48 Hz90 T 420 32 Hz 47 Hz0 T 30 50 Hz 70 Hz791 ~ 970 30 T 90 40 Hz 59 Hz90 T 420 40 Hz 59 Hz0 T 30 52 Hz 72 Hz970 above 30 T 90 40 Hz 59 Hz90 T 420 40 Hz 59 Hz2. After 420 minutes, the operation restarts again from the beginning.3. The operation will restart the above control whenever remote controller setting temperature or fan speed setting is changed.8.2.3. Protection Control For Heating Operation8.2.3.1. Intake Air Temperature ControlCompressor will operate at Max freq 67 Hz if either one of the below conditions occur:1. When the indoor intake air temperature is less than 20°C and remote control setting fan speed is lower Me-.2. When the indoor intake air temperature is 30°C or above.40CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKEThis document is protected (secured) by www.nettovarmepumpar.se