8.2. Protection Control Features8.2.1. Protection Control For All Operations8.2.1.1. Time Delay Safety Control1. The compressor will not start for three minutes after stop of operation.2. This control is not applicable if the power supply is cut off for 20 seconds and on again or after 4-way valve deices condition.8.2.1.2. 30 Seconds Forced Operation1. Once the compressor starts operation, it will not stop its operation for 30 seconds.2. However, it can be stopped using remote control or Auto Switch at indoor unit.8.2.1.3. Total Running Current Control1. When the outdoor unit total running current (AC) exceeds X value, the frequency instructed for compressor operation will bedecreased.2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased.3. However, if total outdoor unit running current exceeds Y value, compressor will be stopped immediately for 3 minutes.Model E9DK E12DKOperation Mode X (A) Y (A) X (A) Y (A)Cooling/Soft Dry (A) 4.0 16.8 5.4 16.8Cooling/Soft Dry (B) 3.6 16.8 5.0 16.8Heating 5.5 16.8 8.4 16.84. The first 30 minutes of cooling operation, (A) will be applied.35CS-E9DKEW CU-E9DKE / CS-E12DKEW CU-E12DKEThis document is protected (secured) by www.nettovarmepumpar.se