276 Using the System2 Touch a distribution group. A keyboard window like the one shown above appears. Use the keyboardto enter a distribution group number and to select the product type from among PAC, GHP and HOT.Select “Simple” or “Load” in the distribution methods.* Refer to “10. Calculating air conditioner distribution” for details.The tenant set at “Load” distribution will have its “No” box display in light blue.* The distribution group number range is from 1 to 8.* This button is invalid when “No Distrib.” has been set. (Refer to Main Sub1155 )* The distribution group column set at loaded distribution has no product type such as “PAC” and “GHP”displayed.* Make manual cut-off in advance to change the distribution method.3 Press the Type button to select “PAC” or “GHP” for the following unit that is unable toautomatically recognize product type.- Interface AdaptorThis is only for “Simple distribution” setting.4 Specify which distribution method, “Simple” or “Load,” to apply to the selected distribution group.5 Touch Set to confirm the setting, or Cancel to cancel it.• PAC, GHP, and HOT cannot be mixed in the same group. Set up a separate distribution group for eachtype.• HOT multi units cannot be recognized automatically (they are recognized as PAC). Manually set theproduct type to HOT.• HOT Tenants cannot be set at the “Load” distribution.• “Load” distribution tenants cannot be set at “HOT”.• Air conditioners unadaptable to loaded distribution cannot be set at “Load” Distribution.• Interface Adaptors are also unadaptable to loaded distribution.Main Sub 3355