808 Connection of External Signals8.2 All Stop InputYou can stop all connected units automatically by connecting external signals (for example, fromfire-alarm detectors.)All stop input is available only for managed (“target”) units. It does not affect units which have beendesignated as not managed (“Not target”) or individually operated (“Indiv Op”).1) Input locationThe communications connector panel on the side of the Intelligent Controller or on an optionalcommunication adaptor connected to the Intelligent Controller:DI1 (No. 17), DI-COMM (No.16)2) OperationWhile the input is asserted ON, a stop signal is sent periodically (once per minute) to all indoorunits.3) DisplayThis message disappears when normal status is restored.8.3 All Start InputYou can start all connected units automatically by connecting external signals.All start input is available only for managed (“target”) units. It does not affect units which have beendesignated as not managed (“Not target”) or individually operated (“Indiv Op”).1) Input locationThe communications connector panel on the side of the Intelligent Controller or on an optionalcommunication adaptor connected to the Intelligent Controller:DI2 (No.18), DI-COMM (No.16)2) OperationWhen inputting ON from OFF, the operation signal will be transmitted to all the indoor units.When both “All stop input” and “All start input” are set ON simultaneously, only “All stop input” is enabled.