5.2 Setting the Switches of the Unit5-35.2 Setting the Switches of the UnitFor using the FP7 MW Unit as W2 link unit, the switches on the front of the unit need to be set. Mode setting switchEach mode is set with the four dip switches on the front of the unit.ON OFF1234No. Item Range1 Operationmode OFF: Non-PLC link mode, ON: PLC link mode2 Mode Set 2 to ON and 3 to OFF. The unit operates as the unit for "MEWNET-W2".34 Baud rate For "MEWNET-W2", set it to OFF for 500 kbps and ON for 250 kbps.(Note 1): All the switches are set to OFF at the factory.(Note 2): Be sure the power is off when changing the switches. Unit number selectorSpecify the own unit number by the two rotary switches on the front of the unit.02531487960253148796UNITNO.Range Description01 to 32 For target unit of PLC link01 to 64 For the data transfer target units (Note 1)00 When setting it in the configuration of the tool software or user program (PMSET/pPMSETinstruction).(Note 1): It indicates the range that can be specified. The range of units that can be actually connected is up to 32units.(Note 2): Be sure the power is off when changing the switches.