22Parity selection Even parity• Selects the parity.• Not available if Serial communication (option) is not added orif is selected during Communication protocol selection.• No parity: , Even parity: , Odd parity:Stop bit selection 1• Selects the stop bit.• Not available if Serial communication (option) is not added orif is selected during Communication protocol selection.• Selecting item: (1) or (2)5.6 Auxiliary function setting mode 2In the PV/SV display mode, if the and keys are pressed for approx. 3seconds, Auxiliary function setting mode 2 can be selected.The set value can be increased or decreased by pressing the or key.If the key is pressed, the set value is registered and the next setting item isselected.Character(PV display) Name, Function, Setting range Default value(SV display)Input type selection• The input type can be selected fromK (–200 to1370 )thermocouple (10 types), RTD (2 types), DC current (2 types) andDC voltage (4 types) and the unit / .Input type Input range–200 to 1370 : –320 to 2500 :K –199.9 to 400.0 : –199.9 to 750.0 :J –200 to 1000 : –320 to 1800 :R 0 to 1760 : 0 to 3200 :S 0 to 1760 : 0 to 3200 :B 0 to 1820 : 0 to 3300 :E –200 to 800 : –320 to 1500 :T –199.9 to 400.0 : –199.9 to 750.0 :N –200 to 1300 : –320 to 2300 :PL- 0 to 1390 : 0 to 2500 :C(W/Re5-26) 0 to 2315 : 0 to 4200 :–199.9 to 850.0 : –199.9 to 999.9 :Pt100 –200 to 850 : –300 to 1500 :–199.9 to 500.0 : –199.9 to 900.0 :JPt100 –200 to 500 : –300 to 900 :4 to 20mA DC –1999 to 9999:0 to 20mA DC –1999 to 9999:0 to 1V DC –1999 to 9999:0 to 10V DC –1999 to 9999:1 to 5V DC –1999 to 9999:0 to 5V DC –1999 to 9999: