KW8M Eco-POWER METER21Stand-by alarm setting mode 1 *It is only when “AL-S” is selected on unit for pulse output setting mode.Set a ratio (for the rated current) of current used for threshold value to judge stand-by powerusing - △>, ▽>, < >, < >.(1.0 to 100.0) Increase valueDecrease valueShift place to setShift place to set↓Stand-by alarm setting mode 2 *It is only when “AL-S” is selected on unit for pulse output setting mode.Set a time used for threshold value to judge stand-by power using
- △>, ▽>, < >, < >.( 0 to 9999 minutes) Increase valueDecrease valueShift place to setShift place to set* “0”: Alarm is always output at the time when judging the stand-by power.* “1 to 9999”:Alarm is output at the time when passing the setting time with the stand-by power.The alarm can be reset by pressing with display of instantaneous electric power, current, voltage,frequency and PF. After reset the alarm, start to monitor the stand-by power again.↓Preset value setting mode *It is only when “Cnt” is selected on unit for pulse output setting mode.Display changes to set an alarm value after “Cnt” is displayed at the upper line for 1 sec.Set preset value to output using
- △>, ▽>, < >, < >( 0 x Prescale value to99999999 x Prescale value)Increase valueDecrease valueShift place to setShift place to setOver 9 digits, it shifts to the upper digit.After1sec.When prescale value is aninteger.When prescale value is to twoplaces of decimals.When prescale value is to threeplaces of decimals.↓ITEM△SHIFT▽ITEM△SHIFT▽ITEM△SHIFT▽