KW8M Eco-POWER METER244.2.3 MODE3(Mode for setting of each parameter for serial communication (RS485))Protocol setting mode PROTMode defines communication protocol of main unit via serial communication (RS485).・Select from MEWTOCOL / MODBUS(RTU).Station number setting mode NOMode defines an individual station no. for each unit when two or more units communicate viaserial communication (RS485).・It can be set the range of 1 to 99.Transmission speed (Baud rate) setting mode SPDMode defines serial communication (RS485) transmission speed. Define the transmissionspeed according to the master’s (PLC etc.).・Select from 19200/38400/2400/4800/9600[bit/s].Transmission format setting mode FMTMode defines serial communication (RS485) transmission format (Data length, Parity).Define the transmission format according to the master’s (PLC etc).・Select from 8bit-o/7bit-n/7bit-E/7bit-o/8bit-n/8bit-E.“n (none)” means parity is not available.“E (Even)” means parity is even number.“o (odd)” means parity is odd number.*With MODBUS (RTU) protocol, it works only with 8bit.Response time setting mode RESPMode defines serial communication (RS485) response time of main unit.When command is received, it sends response after setting response time passes.・It can be set the range of 1 to 99 ms. (initial: 5)MODE3 Setting flow chartMonitor↓MODE 1 display↓- △> 2 timesMODE 3 display↓Protocol setting modePress
- △>, ▽> to change MEWTOCOL ⇔ MODBUS(RTU).MEWTOCOL MODBUS (RTU)↓