343.3.3 Aquarea basic configuration(only needed for connection via Bus)The HPM controller serves as a substitute for the Aquarea operating unit. Therefore,all parameter adjustments needed for initial installation of the heat pump must beperformed via the menu structure of the HPM. This includes necessary basicconfiguration and parameters as these are described in the operating and servicemanuals of the Panasonic heat pump(s).To do this, press “OK” in the default menu and open the “MCR/BMS” menu. Selectthe item “heat producer” using “DOWN” and enter the menu using “OK”.Depending on the system diagram loaded (one or more heat pumps) the menustructure of the heat pump module will either be automatically displayed, or it will benecessary to select heat pump 1-3 by using “UP”, “DOWN” and “OK”.x In the menu for the heat pump, select the menu “function” using “DOWN” and“OK”.x In the “function” menu, select the menu item “Aquarea” using “DOWN” and“OK”.x In the “Aquarea” menu, select the menu “settings” using “DOWN” and “OK”.This menu contains the most important parameters, displayed in the table below withtheir default values. Some of the parameters will already have been automaticallyadjusted when the system diagram was selected (e.g. DHW tank included or not):Name Info text Range / default valueThermos Room thermostat 0:no, 1:yesTank Tank Connection 0:no, 1:yesSolarPrio Solar Priority 0:no, 1:yesHeatPrio Heating Priority 0:no, 1:yesSteril. Sterilization 0:no, 1:yesbasPanH bas pan heater 0:no, 1:yesCoolPrio Cooling Priority 0:no, 1:yesAntiFr Antifreezing 0:no, 1:yesOpInt Operation Interval range: 30-600 min, default: 180 minTankInt Tank heat Interval range: 5-95 min, default: 30 minBoostDel Booster Delay range: 20-95 min, default: 60 minSterTemp Sterilisation boiling temperature range: 40-75 °C, default: 70 °CSterTime Sterilization continuing time range: 5-60 min, default: 10 minHeaterC Heater Capacity range: 0, 3, 6 ,9 KW, default: 0 kWOutTOn Outdoor temp heater on range: -15-20 °C, default: 0 °CTable 3.4: Aquarea setting parametersAfter adjusting the parameters, the power supply for the heat pump must be switchedoff in order to connect the adapter cable PAW-HPINT-x to the main PCB inside theheat pump (instead of the cable coming from the operating unit) The other side of theadapter cable must be connected to the BUS interface of the HPM controller. The heatpump will emit a beep if the connection was successful.3.3.4 Domestic hot water – SetpointsIf setpoints differing from the basic values (45°C) should exist for the domestic hotwater tank, these can be adjusted. Different values for occupation times 1…4 can beselected, as well as non-occupation time and special non-occupation time (holiday).