414.3 Table of measuring values of the sensorsThe HPM controller primarily works with standard PT1000 resistor sensors. In orderto test the sensor, both wires of the connection cable must be disconnected from theHPM controller, after which a temperature-dependent resistor value can then bemeasured with a multimeter. The measured value must correspond with the raw valueof the terminal to which the sensor will be connected again. The raw value can befound in the menu “configuation / inputs / term.xx”. To reach the configuration menu,it is necessary to enter the highest access code for service technicians.Temp.(°C)Raw value(kOhm)Temp.(°C)Raw value(kOhm)Temp.(°C)Raw value(kOhm)Temp.(°C)Raw value(kOhm)-28 0.890 2 1.008 32 1.125 62 1.240-26 0.898 4 1.016 34 1.132 64 1.248-24 0.906 6 1.023 36 1.140 66 1.255-22 0.914 8 1.031 38 1.148 68 1.263-20 0.922 10 1.039 40 1.155 70 1.271-18 0.929 12 1.047 42 1.163 72 1.278-16 0.937 14 1.055 44 1.171 74 1.286-14 0.945 16 1.062 46 1.179 76 1.294-12 0.953 18 1.070 48 1.186 78 1.301-10 0.961 20 1.078 50 1.194 80 1.309-8 0.969 22 1.086 52 1.202 82 1.317-6 0.976 24 1.093 54 1.209 84 1.324-4 0.984 26 1.101 56 1.217 86 1.332-2 0.992 28 1.109 58 1.225 88 1.3400 1.000 30 1.117 60 1.232 90 1.347