77-2. List of Simple Setting ItemsItem code Item Setting dataNo. DescriptionFilter sign ON time(filter life time)0000 Not displayed0001 150 hours0002 2,500 hours0003 5,000 hours0004 10,000 hours0005 Use the filter clogging sensor.Degree of filter fouling0000 Standard (setting at time of shipping)0001 Highly fouled(Filter sign ON time is reduced to one-half the set time.)Central controladdress0001 Central control address 10002 Central control address 20003 Central control address 30064 Central control address 640099 No central control address set (setting at time of shipping)Operating modepriority change0000 Normal ( setting at time of shipping)0001 PriorityFan speed whenheating thermostat isOFFCompressor ON Compressor OFF0000 Lo 1 min., LL 3 min. LL0001 Lo LL0002 LL LL0004 Lo 1 min., LL 3 min. Lo0005 Lo Lo0006 LL LoHeating intaketemperature shift0000 No shift0001 Shifts intake temperature 1 °C down.0002 Shifts intake temperature 2 °C down.0003 Shifts intake temperature 3 °C down.0004 Shifts intake temperature 4 °C down.0005 Shifts intake temperature 5 °C down.0006 Shifts intake temperature 6 °C down.Electric heaterinstallation0000 No heater0001 Heater installedHumidifying whenheater thermostat isOFF0000 No (setting at time of shipping)0001 YesPermit/prohibitautomaticheating/cooling0000 Permit0001 ProhibitCool-only 0000 Normal0001 Cool only (Set “1” for item code OD.)NOTE• In order to avoid water leakage and damage to the fan, do not set for humidifying when the thermostat is OFFunless a vaporizing humidifier is used.• Consider the device purpose and type when changing the settings. Incorrect settings may result in malfunction.• Do not change any setting data that does not appear in this list.7-3