1-2915. TRANSPORT AND INSTALL THE OUTDOOR UNITTransporting1. Transport the outdoor unit in its original packaging as close as possible to the installationlocation.2. In the event that the unit needs to be lifted or suspended, use a rope or belt and usecloth or wood as padding to avoid damaging the unit.3. Use the side handles to carry the unit and be careful not to touch the fi n with your handor any objects.Installation1. Read the “Select the outdoor unit installation location” thoroughly before installing theoutdoor unit.2. When installing to a concrete or solid surface, use M10 or a W 3/8 bolts and nuts tosecure the unit. Ensure that it installed upright on a horizontal plane. (Use an anchorbolt for the installation as shown in the diagram below.)3. Avoid installing on the slanted roof.4. In the even where the roof is at risk of receiving oscillations or vibrations, secure the unitwith a seismic isolating mount or vibration absorbing rubber.5. The drain water will be discharged from the unit during heating ordefrosting operation mode.Select an appropriate location with good drainage system. (In thewinter, there is risk of slipping due to freezing, and depending on theinstallation set up there is risk of drain water running overhead.)Please consult us if installing drain elbows.In cold regions (where the outdoor temperature can drop to below0˚ for 2 to 3 consecutive days), the drain water may freeze andmay prevent the fan from operating. For this case, do not use thedrain elbow.More than 25mmMore than50mmMore than 40mmBaseAnchor bolt length(Unit: mm)(Anchor pitch)20.5 412.5 17355.5195.5159230 200 160 350660 159(Anchor pitch)Anchor bolt positionDrain hole ø32**