C-8 CertificationAC890PX Frame MEMCEmissions LimitsConductedFrequency (MHz) DB (μV) Product SpecificQuasi Peak Average EN 61800-3where I ≤100A0.15 - 0.50.5 - 5.05.0 - 30.0decreasing with log of frequency to:10086907090768060Category C3Table 17where I ≥100A0.15 - 0.50.5 - 5.05.0 - 30.0130125115120115105Where these levels are too high and to ensure compatibility with other equipment, EMC filters are available from Parker.RadiatedFrequency (MHz) DB (μV) Product SpecificQuasi Peak EN 61800-330≤ f- ≤230230≤ f- ≤10005060Category C3(Table 18)Measured at 10mWhere these levels are too high and to ensure compatibility with other equipment, Parker can advise on suitable counter-measures.