Parker EME Compax3 device description192-120102 N15 June 2008 27Mains connection Compax3S1xxV2 3ACController type S100V2 S150V2Supply voltage Three phase 3* 230VAC/240VAC80-253 VAC/50-60HzInput current 10Aeff 13AeffMaximum fuse rating per device(=short circuit rating)16 A (MCB miniaturecircuit breaker)20 A (MCB miniaturecircuit breaker)The 3AC V2 – devices must only be operated with three phases!Always switch devices off before wiring them!Dangerous voltages are still present until 5 minutes after switchingoff the power supply!3.3.5.2 Braking resistor / high voltage DC C3S connector X2In this chapter you can read about:Braking resistor / high voltage supply plug X2 for 1AC 230VAC/240VAC devices............ 27Braking resistor / high voltage supply plug X2 for 3AC 230VAC/240VAC devices............ 28Connection of a braking resistor ........................................................................................ 28The energy generated during braking operation is absorbed by the Compax3 sto-rage capacity.If this capacity is too small, the braking energy must be drained via a braking resi-stor.Braking resistor / high voltage supply plug X2 for 1AC230VAC/240VAC devicesPIN Designation1 Reserved2 - braking resistor (not short-circuit protected!)3 PE4 + braking resistor (not short-circuit protected!)5 ReservedBraking operation Compax3S0xxV2 1ACController type S025V2 S063V2Capacitance / storable energy 560μF / 15Ws 1120μF / 30WsMinimum braking- resistance 100Ω 56ΩRecommended nominal power rating 20 ... 60W 60 ... 180WMaximum continuous current 8A 15AThe power voltage DC of two Compax3 1AC V2 devices (230VAC/240VACdevices) must not be connected.Caution!Caution!