7–Removal and ReplacementPower and Cooling Modules7-10 ISR651101-00 EFRU restore completed.Please reboot the system for configuration to take affect.iSR6200 <1> (admin) #> rebootAre you sure you want to reboot the System (y/n): ySystem will now be rebooted...iSR6200 #>Connection to host lost.The replacement blade should now be operational.Power and Cooling ModulesEach iSR6200 chassis blade has a PCM, located on the back side of the chassis.Each PCM consists of one power supply, three fans, and one external status LED.The PCM’s external status LED shows its status: Green = GOOD status, indicating that the PCM is running as expected. Amber = FAULT status, indicating that the PCM has failed.You can remove and replace a failed PCM as described in the following sections: Removing the Failed PCM “Installing the Replacement PCM” on page 7-12Removing the Failed PCMTo remove a failed PCM from the iSR6200 chassis:1. Locate the failed PCM unit on the back side of the iSR6200 chassis. A failedPCM unit shows an amber colored status LED.Figure 7-9 shows the back side of two PCMs installed in a chassisconfigured with two iSR6200 chassis blades. The PCM on the left sideshows its fault indicator in amber, which indicates a FAULT status. The PCMon the right side shows its fault indicator in green, which indicates a GOODstatus.