November 22, 2011 7063-173D Page 47VOYAGEUR Wood InsertRFigure 47.1NOTICE:• Offsets from the vertical, not exceeding 45°, are allowedper Section 905(a) of the Uniform Mechanical Code(UMC).• Offsets greater than 45° are considered horizontal and arealso allowed, providing the horizontal run does not exceed75% of the vertical height of the vent.• Construction, clearance and termination must be in com-pliance with the UMC Table 9C. This installation must alsocomply with NFPA 211.NOTICE: Top sections of chimney must be removable to allowmaximum clearance of 13.5 feet (411cm) from ground levelfor transportation purposes.1. An outside air inlet must be provided for combustion andmust remain clear of leaves, debris, ice and/or snow. Itmust be unrestricted while unit is in use to prevent roomair starvation which can cause smoke spillage and aninability to maintain a fire. Smoke spillage can also setoff smoke alarms.2. Unit must be secured to the mobile home structure.Remove bolts from each side of insert and use plumberstape to secure to structure (a washer may be required).Re-install bolts.3. Unit must be grounded with #8 solid copper groundingwire or equivalent and terminated at each end with N.E.C.approved grounding device.4. The factory-built fireplace must meet (UM)84-HUDrequirements for outside combustion air supply to thefireplace fire chamber and the chimney must be listed toUL103 HT or a listed UL-1777 full length six inch (152mm)diameter liner must be used. It must be equipped with aspark arrestor cap and the outside air must be installedon the insert.5. Refer to page 30 of this manual for clearance tocombustibles and floor protections requirements. Allclearances must be followed precisely.6. Use silicone to create an effective vapor barrier at thelocation were the chimney or other component penetratesto the exterior of the structure.7. Follow the chimney and chimney connector manufacturer’sinstructions when installing the flue system for use in amobile home.8. Burn wood only. Other types of fuels may generatepoisonous gases (e.g., carbon monoxide).9. If unit burns poorly while an exhaust blower is on in home,(i.e., range hood), increase combustion air.10. Installation shall be in accordance with the ManufacturersHome & Safety Standard (HUD) CFR 3280, Part 24.Spark Arestor CapRoof FlashingStorm CollarJoist Shield/Firestop Double WallConnector PipeCAUTIONTHE STRUCTURAL INTEGRITY OF THE MOBILE HOMEFLOOR, WALL AND CEILING/ROOF MUST BE MAINTAINEDDo NOT cut through:• Floor joist, wall, studs or ceiling trusses.• Any supporting material that would affect the structural integ-rity.• NEVER INSTALL IN A SLEEPING ROOM.Consumes oxygen in the room.WARNINGAsphyxiation Risk.WARNINGDo not draw outside combustion air from:• Wall, floor or ceiling cavity• Enclosed space such as an attic or garage• Close proximity to exhaust vents or chimneys.Fumes or odor may resultFire Risk.Asphyxiation Risk.10 Mobile Home Installation