Regency P33 Sunrise TM Gas Fireplace 13INSTALLATIONINSTALLATIONEXTERIOR FLUE TERMINATION LOCATIONSMinimum clearances required for balanced flue terminals orthe fl ue terminals of outdoor appliancesaccording to AS5601-2004 (AGA gas installation code) or NZS 5262 (New Zealand)and local authorities having jurisdiction.Minimum Clearance (mm)a Below eaves, balconies or other projections:- Appliances up to 50 MJ/h input 300- Appliances over 50 MJ/h input 500b From the ground or above a balcony 300c From a return wall or external corner 500d From a gas meter (M) 1000e From an electricity meter or fuse box (P) 500f From a drain or soil pipe 150g Horizontal from any building structure (unless appliance is approvedfor closer installation) or obstruction facing a terminal 500h From any other flue terminal, cowl or combustion air intake 500j Horizontally from an openable window, door, or non-mechanical air inlet, orany other opening into a building, with the exception of sub-floor ventilation(see also Note (I)):- Appliances up to 150 MJ/h input 500- Appliances over 150 MJ/h input 1500k Vertically below an openable window, door, or non-mechanical air inlet,or any other opening into a building, with the exception of sub-floor ventilation(I) For mechanical air inlets, including spa blowers, the clearance 'j' and 'k' shall be 1500 mm in all cases.(II) All distances shall be measured vertically or horizontally along the wall to a point in line with the nearest par to of the terminal.(III) Prohibited area below electricity meter or fuse box extends to ground level.(IV) A flue terminal of this type shall not be located under a roofed area unless the roofed area is fully open on at least two sides and a free flow ofair at the appliance is achieved.(see also Note (I)): see table belowClearance 'k' in mmSpace Heaters All Other AppliancesUp to 50 MJ/hinputUp to 50 MJ/h Over 50 MJ/h inputto 150 MJ/h inputOver 150 MJ/hinput150 500 1000 1500