30Setting an indoor unit address and installation option(Continued)1. Check whether power is supplied or not.- When the indoor unit is not plugged in, there should be additional powersupply in the indoor unit.2. The panel(display) should be connected to an indoor unit to receive option.3. Set the installation option according to the installation condition of an airconditioner.- The default setting of an indoor unit installation option is“020010-100000- 200000-300000”.- Individual control of a remote controller(SEG20) is the function that controls anindoor unit individually when there is more than one indoor unit.4. Set the indoor unit option by wireless remote controller.Setting an indoor unit installation option (suitable for the condition of each installation location)Indoor Unit1(L) F2F12(N)SEG1 SEG2 SEG3 SEG4 SEG5 SEG60 2 -External roomtemperature sensor /Minimizing fan operationwhen thermostat is offCentral control FAN RPMcompensationSEG7 SEG8 SEG9 SEG10 SEG11 SEG121 Drain pump Hot water heater - EEV Step whenheating stops -SEG13 SEG14 SEG15 SEG16 SEG17 SEG182 External controlExternal control output /External heater On or OffsignalS-Plasma ion Buzzer Number of hoursusing filterSEG19 SEG20 SEG21 SEG22 SEG23 SEG243 Individual control of aremote controllerHeating settingcompensation / Removingcondensated water inheating modeEEV Step of stopped unitduring oil return/defrostmodeMotion detect sensor - 1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to ‘USE + 3minute delay’ even if the drain pump is set to 0. 1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using filter(SEG18) will be set to ‘1000hour’ even if the SEG18 is set toexcept for 2 or 6. When setting the option other than above SEG values, the option will be set as “0”. SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central controloption as 0 (Disuse) to exclude the indoor unit from the central control. The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.F4F3F1 F2 V2V1 1(L) 2(N) 21HOTCOILACPOWEROUTDOORCOMMUNICATIONWire RemoteControllerDC 12 V* The output of hot coil terminal is AC 220 V / 230 V(The same as Indoor Unit’s input Power)COM1 COM2(+) L N(-) The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.) 02 series installation option