32Setting an indoor unit address and installation option(Continued)* Advanced function: Controlling cooling/heating current or power saving with motion detect.(*1) Minimizing fan operation when thermostat is off- Fan operates for 20 seconds at an interval of 5 minutes in heat mode.(*2) 1: Fan is turned on continually when the hot water heater is turned on,3: Fan is turned off when the hot water heater is turned on with cooling only indoor unitCooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and fix it as coolmode.(*3) When the following 2 or 3 is used as external heater On/Off signal, the signal for monitoring external contact control will not beoutput.2: Fan is turned on continually when the external heater is turned on,3: Fan is turned off when the external heater is turned on with cooling only indoor unitCooling only indoor unit: To use this option, install the Mode Select switch (MCM-C200) on the outdoor unit and fix it as coolmode.❇ If Fan is set to off for cooling only indoor unit by setting the SEG9=3 or SEG15=3, you need to use an external sensor or wiredremote controller sensor to detect indoor temperature exactly.(*4) Default setting value- 4Way Cassette, Mini 4Way Cassette: 5 °C- Other indoor units: 2 °COption SEG19 SEG20 SEG21 SEG22 SEG23 SEG24Explanation PAGE Individual control of aremote controllerHeating setting compensation / Removingcondensated water in heating modeEEV Step of stoppedunit during oil return /defrost modeMotion detect sensor -RemoteControllerDisplayIndication andDetailsIndication Details Indication Details IndicationDetailsIndication Details Indication DetailsHeating SettingCompensationRemovingCondensatedWater in HeatingMode30 or 1 channel 10 Default (*4) Disuse0 Defaultvalue0 Disuse1 2 °C Disuse 1 Turn out in 30min.without motion2 channel 2 2 5 °C Disuse1Oil returnor Noisedecreasingin defrostmode2 Turn out in 60min.without motion3 channel 3 3 Default (*4) Use (*5) 3 Turn out in 120min.without motion4 channel 44 2 °C Use (*5) 4 Turn out in 180min.without motion5 5 °C Use (*5)5 Turn out in 30min.without motion or*advanced function6 Turn out in 60min.without motion or*advanced function7 Turn out in 120min.without motion or*advanced function8 Turn out in 180min.without motion or*advanced function