31ENGLISHOption No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX 02 series installation option(Detailed)Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6Explanation PAGE MODE Use of robot cleaningUse of external room temperature sensor /Minimizing fan operation when thermostatis offUse of central control FAN RPM compensationRemoteControllerDisplayIndicationand DetailsIndication Details Indication Details Indication Details IndicationDetailsIndication Details Indication DetailsUse ofExternal roomtemperaturesensorMinimizingfan operationwhenthermostatis off0 20 Disuse 0 Disuse Disuse 0 Disuse 0 Disuse1 Use1 Use Disuse1 Use1 RPMcompensation2 Disuse Use (*1)2 High ceiling KIT3 Use Use (*1)Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12Explanation PAGE Use of drain pump Use of hot water heater EEV Step whenheating stopsRemoteControllerDisplayIndicationand DetailsIndication Details Indication Details Indication Details Indication Details Indication Details Indication Details10 Disuse 0 Disuse 0 Defaultvalue1 Use 1 Use (*2)1Noisedecreasingsetting2When anindoor unitstops, drainpump willoperate for3min.2 -3 Use (*2)Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18Explanation PAGE Use of external control Setting the output of externalcontrol/External heater On/Off signal S-Plasma ion Buzzer control Number of hoursusing filterRemoteControllerDisplayIndicationand DetailsIndication Details Indication Details IndicationDetailsIndication Details Indication Details Indication DetailsSetting theoutput ofexternalcontrolExternalheaterOn/Offsignal20 Disuse 0 Thermo on - 0 Disuse 0 Use buzzer 2 1000 Hour1 ON/OFFcontrol 1 Operationon -1 Use 1 Disusebuzzer 6 2000 Hour2 OFF control 2 - Use (*3)3WindowON/OFFcontrol3 - Use (*3)