88Samsung ElectronicsCheck Operation & Amount of Refriherant Automatically Checking5) Cycle status■ Inspection item : Cycle status of Outdoor Unit.■ Error code: None (The resulting report "Undetermined")■ Determine the Cycle status of the each Outdoor Unit.■ If the judgment of Cycle status is "Undetermined" : Checking in accordance with the following order.YesNoNoCommissioning results,is Valve and Pressure sensor normal?NoNoNoIs Discharge Temperature sensor ofcorresponding Outdoor Unit normal?When commissioning, does maintainThermo On status of Indoor Unit?YesIs refrigerant in the system propely?YesComplete[DischargeTemperature sensorresistance value]Temperature(℃)Resistance(Ku)1312108060252010089.0112.0185.0320.0590.02000.02402.03602.05503.0※ Resistance measurement method Afterseparating the Temperature sensorconnector from the PCB, measure theresistance value between the twoterminals.Inspection and measuresof Discharge Temperaturesensor.(Assembly status,connector, resistance, etc.)Confirmation andMeasures.Indoor ventilationAdjusts the refrigerant(Addition / Emitted)