E-17ENGLISH)INSTALLING THE OUTDOOR UNITMH070FXA4B / MH080FXA4B1(L) 2(N) 1(L) 2(N) F1 F2 F1 F2L N1(L) 2(N) F1 F2 1(L) 2(N) F1 1(L) 2(N) F1 1(L) 2(N) F1F21 21 2F1 F2F1 F2F1 F2F1 F21 221F21 2 F1 F2F1 F2F2F1 F2F1 F21 2211 21 2B C B CB C B CAA B C D A BF1 F2 F1 F2C D1(L) 2(N) 1(L) 2(N)A-unit B-unit C-unit D-unitIndoor unitAssembly cableOutdoor unitEarthterminalEarthterminal EarthterminalEarthterminalEarthterminalEarthterminal Earthterminal EarthterminalPower cable to indoor units EarthterminalMain Powersupply cableCommunication cableto indoor units���Cable Type: ACable Type: BCable Type: CThe specification for cables :Model Main Power Supply Cable Indoor Power Supply Cable Communication Cable FUSE MCCB Type GLSpecication Type Specication Type Specication TypeMH040FX*A2BMH040FX*A2CMH050FX*A2BMH050FX*A2CMH18VF1XMH19VF1X3G, 2.5mm2 ormore,H07RN-F� 3G, 1.0mm2 ormore,H07RN-F� 2G, 0.75mm2 ormore,H07RN-F�20A Frame : 30ATrip : 20A 20AMH060FX*A3B 20A Frame : 30ATrip : 25A 25AMH070FX*A4BMH080FX*A4B 30A Frame : 30ATrip : 30A 30AScrew Torque(kgf.cm)Unfasten Torque Tighten TorqueM4 17~30 25~40M5 20~35 30~50 Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply,it must be incorporated in a wire with a contact opening of ≥3mm. The terminal is connected too firmly , the terminal may be damaged.09'FJM_OUTDOOR_28896A_IM_E_11.23.09.indd 17 2009-11-24 9:19:56