E-6PREPARING THE INSTALLATIONDeciding on Where to Install the Air Conditioner (Continued)MH050FXA2B/MH050FXA2CIndoor unit Outdoor unit Power supplyØ, V, Hz020/023/026/035/052 MH050FXA2BMH050FXA2C 1,220-240, 50Unit Outside diameterLiquid Gas020/023/026/035 1/4" 3/8"052 1/2"MH050FXA2B/MH050FXA2C outdoor unit cannot be connected to the following indoor unit combination.-MH052FMEA/MH052FUEAPiping outside diameter(h) (H)A B600 mmminimum1 Room maxlength2 Room total maxlengthMax height betweenindoor unit & outdoor unitMax height betweenindoor unitsDimension 20m 30 m 15m 7.5 mComposition A,B A+B (H) (h)Piping length and the heightMain power switch200 mmor more160 mmor more100 mmor more300 mmminimum300 mmminimum600 mmminimumCAUTION:3 m as minimum pipe length: It will reducenoise and vibration.This value must be increased at 7.5 metersin case it is connected just one indoor unit.System can work with one indoor unit connected, but it is recommended that the TOTAL numberof indoor unit suggested by manufacturer are connected to obtain the maximum performance.The appearance of the unit may be different from the diagram depending on the model.Make at least one round:It will reduce noise and vibrationThe appearance of the unit may be different from the diagram depending on the model.09'FJM_OUTDOOR_28896A_IM_E_11.23.09.indd 6 2009-11-24 9:19:26