E-31ENGLISHPipe Checking Operation (Auto Addressing Mode)Switch the system on and wait for code " " to appear on the display ofthe external unit (this requires approximately 60 seconds **).As soon as code " "displays, press once the red button (K1) shown onthe figure on the side of the page:WARNING !!If the quantity of indoor units connect-ed is lower than maximum connectableto outdoor unit, the rotary switch SW01has to be positioned, in order to select anumber equal to indoor units’ quantityyou connected.After the operations described above have been performed, the system startsin Cooling or Heating mode, depending on the external ambient temperature.After a few minutes (from a minimum of 3 to 5 minutes for the internalunit), the system stops automatically, completing the self-test and addressingprocedure. " " appears on the display of the external unit.20 seconds after the display of " " (that confirms the correct executionof the procedure), the following codes (if four internal units are connected) display in sequence on the display of the external unit:Display 1 Display 2 DescriptionThe outdoor unit is communication correctly togeth-er the indoor unit connected to refrigerant pipe A.The outdoor unit is communication correctly togeth-er the indoor unit connected to refrigerant pipe B.The outdoor unit is communication correctly togeth-er the indoor unit connected to refrigerant pipe C.The outdoor unit is communication correctly togeth-er the indoor unit connected to refrigerant pipe D.At this point it is possible to start the internal unitsin the desired modeIf " "doesn’t display, the procedure has failed and it is thereforenecessary to read ALL the operator’s manual before repeating the operatingdescribed in steps 1-2-3-4.COMPLETING THE INSTALLATIONRed Button K1SW01Display 1 Display 2Display of the external unit During the initial 60 seconds, dis-play 1 shows in sequence: 000102 ...1500...09'FJM_OUTDOOR_28896A_IM_E_11.23.09.indd 31 2009-11-24 9:20:55