VIRDI 4000 TM User’s Manual 48UNION COMMUNITY Co., Ltd. 44-3 Hyundai Topics Building, Bangi-dong,Songpa-gu, Seoul, Korea 138-050, Tel: 82-2-6488-3000, Fax: 82-2-6488-3099,E-Mail:sales@unioncomm.co.kr, http://www.unioncomm.co.kr/eng3.8.4. Wiegand output settings◆ [*] [6] ‘084265’ [ENTER] ◆[4]Wiegand Out:00=None 1=26bit2=34bitDefault setting: ‘0’The default setting is ‘0’. If Wiegand output from the local terminal is needed forexternal access controller with Wiegand input, an administrator can set thissetting as ‘1’ or ‘2’.- In case of ‘1’ setting, “site code [1 byte] and user ID [2 bytes]” are transmittedthrough Wiegand output port. User ID should be set as less than 4 digits.- In case of ‘2’ setting, “site code [1 byte] and user ID [3 bytes]” are transmittedthrough Wiegand output port. User ID should be set as less than 7 digits.※ This setting is not related to external Wiegand reader.※ In cases of ‘1’ or ‘2’ settings, the below-mentioned site code should be set.(0-255):000Default setting: ‘000’An administrator can assign the site code, from 0 to 255, which is transmittedtogether with a user ID.After this setting is complete, press [ENTER] to move to the upper menu.0=Off1=Wiegand2=TerminalDefault setting: ‘0’1. Data input Wiegand data is printed as wiegand2. Input card data from terminal is printed as wiegand3.8.5. System configuration settings1. Set Fn-Key2. Card Reader3. FP-Sensor4. Wiegand5. System Config6. InitializePress [5] for system configuration settings.