7vacon • 76 Commissioning7.1 Commissioning of the driveRead carefully the safety instructions in Chapter 2 and above and follow them.After the installation: Check that both the AC drive and the motor are grounded. Check that the mains, brake and motor cables comply with the requirements given inChapter 5.1.1. Check that the control cables are located as far as possible from the power cables, seeChapter 5.3. Check that the shields of the shielded cables are connected to protective earth markedwith . Check the tightening torques of all terminals Check that the wires do not touch the electrical components of the drive. Check that the common inputs of digital input groups are connected to +24 V or groundof the I/O terminal or the external supply. Check the quality and quantity of cooling air (Chapter 4.2 and Table 12). Check the inside of the AC drive for condensation. Check the installation space for foreign objects. Check that all Start/Stop switches connected to the I/O terminals are in Stop-posi-tion. Before connecting the AC drive to mains: Check mounting and condition of all fusesand other protective devices. Run the Startup Wizard (see the Application Manual).7.2 Running the motorMOTOR RUN CHECK LISTBefore starting the motor, check that the motor is mounted properly and ensurethat the machine connected to the motor allows the motor to be started.Set the maximum motor speed (frequency) according to the motor and themachine connected to it.Before reversing the motor make sure that this can be done safely.Make sure that no power correction capacitors are connected to the motor cable.Make sure that the motor terminals are not connected to mains potential.13006.emf13006.emf13006.emf13006.emf13006.emfPhone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com