9vacon • 94 Technical data, Vacon 100 FLOW9.1.2 Mains voltage 380-500 VNOTE! The rated currents in given ambient temperatures (in Table 32) are achieved only whenthe switching frequency is equal to or less than the factory default.NOTE! For cyclical loads, please contact Vacon for dimensioning.Table 31. Power ratings of Vacon 100 FLOW, supply voltage 380-500 VMains voltage 380-500V, 50-60 Hz, 3~Drive type* Loadability* See Chapter 9.1.3.Motor shaft powerContinuouscurrent I L[A]10% overloadcurrent[A]Max currentI S2s400 Vsupply480 Vsupply10% overload40 °C[kW]10% overload40 °C[hp]MR40003 3.4 3.7 5.2 1.1 1.50004 4.8 5.3 6.8 1.5 2.00005 5.6 6.2 8.6 2.2 3.00008 8.0 8.8 11.2 3.0 4.00009 9.6 10.6 16.0 4.0 5.00012 12.0 13.2 19.2 5.5 7.5MR5 0016 16.0 17.6 24.0 7.5 10.00023 23.0 25.3 32.0 11.0 15.00031 31.0 34.1 46.0 15.0 20.0MR6 0038 38.0 41.8 62.0 18.5 25.00046 46.0 50.6 76.0 22.0 30.00061 61.0 67.1 92.0 30.0 40.0MR7 0072 72.0 79.2 122.0 37.0 50.00087 87.0 95.7 144.0 45.0 60.00105 105.0 115.5 174.0 55.0 75.0MR8 0140 140.0 154.0 210.0 75.0 100.00170 170.0 187.0 280.0 90.0 125.00205 205.0 225.5 340.0 110.0 150.0MR9 0261 261.0 287.1 410.0 132.0 200.00310 310.0 341.0 502.0 160.0 250.0Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com