4vacon • 9 CommissioningTel. +358 (0) 201 2121 • Fax +358 (0)201 212 2054.2 PROFINET IO parameters and monitoring valuesTable 4. PROFINET parametersCode Parameter Min Max Unit Default ID DescriptionP5.9.5.1.1 Protocol in use 0 1 00 = Not in use1 = PROFINET enabled.The parameter is lockedfor editing when thedrive is in RUN state.P5.9.5.1.2 Communicationtime-out 0 65535 s 100 = The time-out isdefined by Master.(= Watchdog time).Table 5. PROFINET monitoring valuesCode Parameter Min Max Unit Default ID DescriptionP5.9.5.2.1 Name of stationA value used to uniquelyidentify the device on thenetwork.This monitoring value isnormally not visible butappears when aPROFINET IO connectionis established.P5.9.5.2.2 Fieldbus protocolstatus 1 31 = Stopped2 = Operational3 = FaultedP5.9.5.2.3 Communicationstatus 0 999 00-99 Number ofmessages with errors.0-999 Number ofmessages withoutcommunication errors.P5.9.5.2.4 Setpoint telegram 1 3 1Telegram used in thesetpoint direction.1 = Vendor-specific 12 = Vendor-specific 23 = Vendor-specific 3P5.9.5.2.5 Actual valuetelegram 1 3 1Telegram used in theactual value direction.1 = Vendor-specific 12 = Vendor-specific 23 = Vendor-specific 3P5.9.5.2.6 Number of processdata 0 8 0The number of additionalprocess data fieldsselected forcommunication.P5.9.5.2.7 Control word 0 FFFFFFFFh 0The latest control word(vendor-specific format)received from the driveapplication. (Can be usedfor debugging purposes.)P5.9.5.2.8 Status word 0 FFFFFFFFh 0The latest status word(vendor-specific format)received from the driveapplication. (Can be usedfor debugging purposes.)