Description of Groups vacon • 22Service support: find your nearest Vacon service center at www.vacon.com22.3.6 Group Analogue outputs: Menu PAR G6Code Parameter Min Max Unit Default ID DescriptionP6.1 Analogue outputfunction 0 8 2 3070 = Not used (fixed 100%)1 = Freq. reference (0-fmax)2 = Output freq. (0 -fmax)3 = Motor speed (0 - Speedmax)4 = Output current (0-InMotor )5 = Motor torque (0-TnMotor)6 = Motor power (0-P nMotor )7 = PID output (0-100%)8 = Filedbus(0-10000)P6.2 Analogue outputminimum 0 1 0 310 0 = 0V1 = 2VP6.3 Analogue output scale 0,0 1000,0 % 100.0 311 Scaling factorP6.4 Analogue output filtertime 0.00 10.00 s 0.10 308Filtering time of analogue out-put signal.0 = No filteringP6.5 Exp. AO1 function 0 8 2 1844 See P5.1P6.6 Exp. AO1 minimum 0 1 0 1845 0 = 0 mA1 = 4 mAP6.7 Exp. AO1 Output scale 0,0 1000,0 % 100.0 1846 Scaling factorP6.8 Exp. AO1 filter time 0.00 10.00 s 0.10 1847Filtering time of analogue out-put signal.0 = No filteringP6.9 Exp. AO2 function 0 8 2 1848 See P6.1P6.10 Exp. AO2 minimum 0 1 0 1849 0 = 0 mA1 = 4 mAP6.11 Exp. AO2 Output scale 0,0 1000,0 % 100.0 1850 Scaling factorP6.12 Exp. AO2 filter time 0.00 10.00 s 0.10 1851Filtering time of analogue out-put signal.0 = No filteringTable 11. Analogue outputs parameters.NOTE!Visibility of the group depends on P1.16.Parameters P6.5 - P6.18 are shown only when expansion board OPTB4 or OPTBFis installed.Parameters P6.9 - P6.12 are shown only when expansion board OPTB4 isinstalled.