Description of Groups vacon • 32Service support: find your nearest Vacon service center at www.vacon.com22.3.13 Group temperature measurement: Menu Par G13Code Parameter Min Max Unit Default ID DescriptionP13.1 Temperature unit 0 1 0 1863 0 = °C1 = °KP13.2 Superv/Fault sensorselect 0 6 0 18730= T11= T22= T1 + T23= T34= T3 + T15= T3 + T26= T3 + T2 + T1P13.3 Supervision mode 0 2 1 18640: not used1: over threshold2: below thresholdP13.4 Fault mode 0 2 0 18650: not used1: over threshold2: below thresholdP13.5 Supervision level -30.0223.2200.0473.2°C°K 80.0 1867 Threshold for supervisionP13.6 Fault level -30.0223.2200.0473.2°C°K 100.0 1866 Threshold for fault (F56 faultcode)P13.7 Superv/fault Hysteresis 0.0 50.0 °C°K 2.0 1868 Hysteresis for state changeP13.8 Refer/Actual sensorselect 0 6 0 18690= T11= T22= T33= max(T1,T2)4= min(T1,T2)5= max(T1, T2, T3)6= min(T1, T2, T3)P13.9 Min Ref/Actualtemperature-30.0223.2200.0473.2°C°K 0.0 1870 Temperature for min reference/actualP13.10 Max Ref/Actualtemperature-30.0223.2200.0473.2°C°K 100.0 1871 Temperature for max reference/actualTable 18. Temperature measurement parameters.NOTE! This group is hidden when board OPTBH is not installed.