vacon • 67 Parameter description33.10 AutoresetP10.1 AUTOMATIC FAULT RESET0: Disabled1: EnabledThe automatic reset function deletes fault state when the fault cause has been eliminated andthe wait time P10.2 has elapsed. Parameter P10.4 determines the maximum number of auto-matic resets that can be effected during the trial time set by parameter P10.3. The time countstarts from the first automatic reset. If the number of faults detected during the trial time ex-ceeds the values of trials, the fault status becomes permanent and a reset command is need-ed.P10.2 WAIT TIMETime after which the converter attempts to restart the motor automatically after the fault hasbeen eliminated.P10.3 T RIAL TIMETotal time for reset attempts.P10.4 AUTOMATIC RESET TRIESTrials attempted during time P10.3.P10.5 S TART FUNCTIONStart function after an automatic fault reset.0: Start with ramp1: Flying start2: As defined in P1.13P10.6 UNDERVOLTAGE FAULT AUTORESET0: Disabled1: EnabledEnable/disable autoreset function for Undervoltage fault.P10.7 OVERVOLTAGE FAULT AUTORESET0: Disabled1: EnabledEnable/disable autoreset function for Overvoltage fault.P10.8 OVERCURRENT FAULT AUTORESET0: Disabled1: EnabledEnable/disable autoreset function for Overcurrent fault.