To add other languages to the panel, see Upgrading Languages on page 340. To add otherlanguages to a keypad, see the documentation for that keypad. Installation guides are availableat http://www.spcsupportinfo.com/connectspcdata/userdata.8. Enter the DATE and TIME.The system scans the X-BUS for modems.9. Enable SPC CONNECT to allow a panel to communicate with https://www.spcconnect.comonce the panel IP address is configured.10. Enable DHCP to automatically assign an available network IP address to the panel. If you'veenabled SPC CONNECT and DHCP, an SPC CONNECT ATS is now added to the panel tocomplete the connection to https://www.spcconnect.com11. For DHCP enabled panels, the automatically assigned IP address displays in the IP ADDRESSmenu. If DHCP is not enabled, the default IP address displays. Choose SELECT to continue. InEngineer Programming mode, under COMMUNICATIONS, you must manually enter the staticIP address for the panel.12. Choose the X-BUS addressing mode:- MANUAL: is recommended for most installation types, especially when doing apreconfiguration.- AUTO: is recommended only for very small installations.13. Choose the installation topology: LOOP (Ring) or SPUR (Chain).The system scans for the quantity of keypads, expanders, door controllers and available zoneinputs.14. Press NEXT to scan all X-BUS devices.PROGRAMMING MODE will be displayed.The Start-up setting is complete.15. Check the alerts in the menu SYSTEM STATUS > ALERTS. Otherwise you will not be allowedto exit the Engineer Mode.16. Configure the system by keypad or web browser.See alsoDomestic, Commercial and Financial mode default settings on page 36614.4 Creating system usersBy default the SPC system only allows engineer access on the system. The engineer must createUsers to allow on-site personnel to set, unset, and perform basic operations on the system as required.Users are restricted to a set of panel operations by assigning them to specific User Profiles.The system allows all user PINs within the allowed PIN range, that is, if a 4 digit PIN is used then alluser PINs between 0000 and 9999 would be permissible.See Users on page 135 or Users on page 196.The ability to grant manufacturer access to the system (for example, allow a firmware upgrade ofthe panel) is configured as a user right for a user profile. If a user is going to be enabling firmwareupgrades, ensure that the user has the correct profile for this purpose.See alsoEngineer PINs on page 106SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Starting the system© Vanderbilt 2018 108 A6V10276959-d11.2018