17.10.1.2 Editing an output1. Select Configuration > Hardware > Controller.2. Configure the fields as described in the table below.Output Type l System Output: Select the type from the dropdown menu. (See Outputstypes and output ports on the facing page.)l Area Output: Only if (multiple) Areas is activated in menu PanelSettings > System Settings > Options. Select an area and the type ofsystem output for this area. (See Outputs types and output ports on thefacing page.)l Zone Mapping: Select which zone should be mapped.l Mapping Gate: Select which mapping gate should be mapped.l Door Output: Select the door number and the type of system output forthe door. (See Outputs types and output ports on the facing page.)l Keyswitch: Select the node ID for the required keyswitch and the requiredkey position to map to this output.Description Enter a text describing the output (max. 16 characters). This text will alsoappear on the browser and keypad.OutputConfigurationl Mode: Select the operational mode. Continuous follows output type;Pulsed toggles on and off when output type is active; Momentarygenerates a pulse when output type activates.l Retrigger: Tick the box to retrigger momentary outputs.l On Time: Enter the On time that applies to momentary and pulsedoutputs.l Off Time: Enter the Off time that applies to pulsed outputs.l Invert: Tick this box to invert the physical output.l Log: Tick this box to log the output state changes to the event log.l Calendar: Select if necessary the desired calendar. See Calendars onpage 284.SPC4xxx/5xxx/6xxx – Installation & Configuration Manual Engineer programming via the browser© Vanderbilt 2018 231 A6V10276959-d11.2018