396 Set up with the display and adjustment moduleVEGAPULS 69 • Foundation Fieldbus47251-EN-160815This menu item is used to select the national language for further pa-rameter adjustment. You can change the selection via the menu item"Setup - Display, Menu language".With the "OK" key you move to the main menu.6.4 Parameter adjustment - Quick setupTo quickly and easily adapt the sensor to the application, selectthe menu item "Quick setup" in the start graphic on the display andadjustment module.Select the individual steps with the [->] key.After the last step, "Quick setup terminated successfully" is displayedbriefly.Information:The echo curve of setup is stored automatically during the quicksetup.The return to the measured value indication is carried out through the[->] or [ESC] keys or automatically after 3 sYou can find "Extended adjustment" in the next sub-chapter.6.5 Parameter adjustmentThe instrument is adapted to the application conditions via the pa-rameter adjustment. The parameter adjustment is carried out with anadjustment menu.The main menu is divided into five sections with the following func-tions:Setup: Settings, for example, for medium, application, vessel, adjust-ment, dampingDisplay: Language setting, settings for the measured value indicationas well as lightingDiagnosis: Information, e.g. on instrument status, pointer, measure-ment certainty, simulation, echo curveFurther settings: e.g. instrument units, unit SV2, false signal sup-pression, linearization, date/time, reset, copy sensor dataSelection of nationallanguageMain menu