49PEM-X1OPERATING MANUALVERSION 09/2012 ORDER NUMBER DOC 23260209.1 OVERVIEW OF INSPECTIONSSection Type of inspection Requirements InspectionbyType of inspection Inspectioninterval1 Effectiveness of technicalventilation checkEffectiveness of technicalventilation checkUP/BP MEMeasurements of air flow speed /air quantitiesCheck the differential pressureindicator.Continuously2 Interlock between technicalventilation and high-voltage,compressed air and coatingmaterial supplyThe technical ventilation shouldbe interlocked such that the high-voltage cannot be switched onwhile the technical ventilation isnot working effectively.BP FUTest whether the system is safelystopped and the material supply,supply air and high-voltageare switched off when theventilation is shut down.Annually3 Effectiveness of groundingmeasuresAll the system's conductiveelements, such as floors, walls,ceilings, protective grating,transport equipment, work pieces,powder containers, machines orconstruction parts etc. in the sprayarea, with the exception of partswhich carry high-voltage duringoperation, must be connected tothe grounding system. Parts ofthe booth must be grounded inaccordance with EN 12215.BP SI/ME/SÜVisual check of groundconnections, perform functiontest on grounding switch,measurement of groundingresistors.WeeklyKey:HE = ManufacturerAG = EmployerBP = Capable personBSB = Fire safety engineerEFK = ElectricianUP = Trained personFU = Function inspectionME = MeasurementOP = Standard inspectionSI = Visual inspectionSÜ = Continuous inspectionTP = Technical inspection