WAGO-I/O-SYSTEM 750 XTR Connect Devices 35750-xxxx/0040-xxxx Design Notes /XTRManualVersion 1.2.0Pos : 32 /Serie 750 ( WAGO-I/O-SYST EM)/Ans chli eßen/Leiter an Pus h-in CAGE CLAMP® ansc hließ en - Ü bersc hrift 2 und T ext @ 6\mod_1258964749000_21.doc x @ 44640 @ 2 @ 16.4 Connecting a Conductor to the Push-in CAGECLAMP ®The Push-in CAGE CLAMP ® connection is appropriate for solid, stranded andfinely stranded conductors.Only connect one conductor to each Push-in CAGE CLAMP® connection!Only one conductor may be connected to each Push-in CAGE CLAMP ®connection.Do not connect more than one conductor at one single connection!If more than one conductor must be routed to one connection, these must beconnected in an up-circuit wiring assembly, for example using WAGO feed-through terminals.Terminate both solid and stranded or ferruled conductors by simply pushing themin - no tool required. For all other types of conductors, Push-in CAGE CLAMP ®must be opened for connection with an operating tool with a 2.5 mm blade (orderno. 210-719).1. To open the Push-in CAGE CLAMP ® insert the actuating tool into theopening above the connection.2. Insert the conductor into the corresponding connection opening.3. To close the Push-in CAGE CLAMP ® simply remove the tool - theconductor is then clamped firmly in place.Figure 12: Connecting a Conductor to a Push-in CAGE CLAMP ®Pos : 33 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1