Fieldbus Controller 750-841 • 85Starting up an ETHERNET TCP/IP fieldbus nodeWAGO-I/O-SYSTEM 750ETHERNET TCP/IPYou can download a free copy of the WAGO’s BootP server over the Internetunder at http://www.wago.com/-“Service“/“Downloads“/“Software“/“ELECTRONICC“/-‘WAGO BootPServer V1.0 Windows 95/NT - ZIP Archiv‘.NoteThe IP address can be allocated under other operating systems (e.g. underLinux) as well as with any other BootP servers.AttentionThe IP address can be allocated in a direct connection via a crossover cable orvia a parallel cable and a hub. An allocation over a switch is not possible.BootP tableNoteA prerequisite for the following steps is the correct installation of the WAGOBootP server.1. To start the BootP server, click on the Start menu item Programs/WAGOSoftware/WAGO BootP Server.2. After the BootP Server is started, click on the Edit Bootptab buttonlocated on the right hand side of the display. An editable file will appear inWindows NotePad (bootptab.txt). This file is a database for the BootPserver. The file contains two examples for the allocation of an IP address,the example commands are directly after the following comment lines:- "Example of entry with no gateway"- "Example of entry with gateway"Fig. 3-12: BootP table p012908dThe examples mentioned above contain the following information:Declaration Meaningnode1,node2Any name can be given for the node here.ht=1 Specify the hardware type of the network here.The hardware type for ETHERNET is 1.