WAGO-I/O-SYSTEM 750 Mounting 47750-493 3-Phase Power Measurement ModuleManualVersion 1.2.0Pos : 72 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Monti eren/M ontier en - Übersc hrift 1 @ 3\mod_1225446744750_21.doc x @ 24900 @ 1 @ 16 MountingPos : 73.1 /Serie 750 (WAGO-I/O-SYST EM)/M ontieren/D emontieren/M ontagerei henfolge @ 3\mod_1231770210031_21.doc x @ 25992 @ 2 @ 16.1 Mounting SequenceFieldbus couplers/controllers and I/O modules of the WAGO-I/O-SYSTEM750/753 are snapped directly on a carrier rail in accordance with the Europeanstandard EN 50022 (DIN 35).The reliable positioning and connection is made using a tongue and groovesystem. Due to the automatic locking, the individual devices are securely seatedon the rail after installation.Starting with the fieldbus coupler/controller, the I/O modules are mountedadjacent to each other according to the project design. Errors in the design of thenode in terms of the potential groups (connection via the power contacts) arerecognized, as the I/O modules with power contacts (blade contacts) cannot belinked to I/O modules with fewer power contacts.Pos : 73.2 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Vorsic ht/Vorsicht: Verl etz ungsgefahr durc h s charfkantige M ess er kontakte! @ 6\mod_1256193279401_21.doc x @ 43414 @ @ 1Risk of injury due to sharp-edged blade contacts!The blade contacts are sharp-edged. Handle the I/O module carefully to preventinjury.Pos : 73.3 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Achtung/Achtung: Bus kl emmen nur in vorgesehener R eihenfolg e stec ken! @ 6\mod_1256194177073_21.doc x @ 43429 @ @ 1Insert I/O modules only from the proper direction!All I/O modules feature grooves for power jumper contacts on the right side. Forsome I/O modules, the grooves are closed on the top. Therefore, I/O modulesfeaturing a power jumper contact on the left side cannot be snapped from the top.This mechanical coding helps to avoid configuration errors, which may destroythe I/O modules. Therefore, insert I/O modules only from the right and from thetop.Pos : 73.4 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Hinweis/Hi nweis: Busabsc hluss nicht vergess en! @ 6\mod_1256194225557_21.doc x @ 43432 @ @ 1Don't forget the bus end module!Always plug a bus end module 750-600 onto the end of the fieldbus node! Youmust always use a bus end module at all fieldbus nodes with WAGO-I/O-SYSTEM 750 fieldbus couplers/controllers to guarantee proper data transfer.Pos : 73.5 /Dokumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1